300 Series Specifications
|
| Type of Design |
Silicon Oxide VaristorTM
|
| Maximum current |
100,000 amps |
| Maximum energy |
3,000 joules per pole
|
| Maximum number of surges |
Unlimited |
| Response time one milliamp test |
5 nanoseconds |
| Response time to clamp 10,000 amps |
10 nanoseconds |
| Response time to clamp 50,000 amps |
25 nanoseconds |
| Leak current at double the rated voltage |
none |
| Leads |
36" #12 THHN |
| Case material |
PVC |
| Locknut and Washer |
1/2" - 3/4" |
| Category B & C and Type 1 & 2 |
Conduction Characteristics
|
8 x 20 microsecond wave shape ANSI IEEE NEMA Standard |
| Discharge Current |
5000 A |
10000 A |
20000 A |
40000 A |
60000 A |
80000 A |
100000 A |
Clamping Voltage (Line to Neutral)
|
240 V |
480 V |
840 V |
1300 V |
2000 V |
3000 V |
4000 V |
| Unlimited Operations |
One Operation |
Weatherproof N-4
Case Dimensions:
2 1/4" Diameter
4 1/2" High
LA302 - For 120-250 V, Single Phase,
3 Wire ServiceRated voltage 125-250 Volt, three wire service. Used when two hot wires of a single-phase system are to be protected.
INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wires to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal framework of the equipment to be protected or make a ground source per NEC Article 250.