LA601   2 wire single phase: 18" leads, 0-650 volts

Delta

LA601 2 wire single phase: 18" leads, 0-650 volts

$57.00

Weatherproof N-4
Case Dimensions:
2 1/4" Diameter
4 1/2" High

 

600 Series Specifications

Type of Design Silicon Oxide VaristorTM
Maximum current 100,000 amps
Maximum energy

3,000 joules per pole

Maximum number of surges Unlimited
Response time one milliamp test 5 nanoseconds
Response time to clamp 10,000 amps 10 nanoseconds
Response time to clamp 50,000 amps 25 nanoseconds
Leak current at double the rated voltage none
Leads 36" #12 THHN
Case material PVC
Locknut and Washer Furnished


Conduction Characteristics

8 x 20 microsecond wave shape
ANSI IEEE NEMA Standard
Discharge Current 5000 A 10000 A 20000 A 40000 A 60000 A 80000 A 100000 A
Clamping Voltage
(Line to Neutral)
450 V 920 V 1040 V 1500 V 2300 V 4000 V 5000 V
Unlimited Operations One Operation

LA601 - For 440-600 Volt Single
Phase 2 Wire Service


Rated voltage 240-480-600 Volt, two wire service. Used when one hot wire of a three-phase system is to be protected; one wire for a control circuit, or three arrestors for protecting three phases.

INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wire to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal framework of the equipment to be protected or make a ground source per NEC Article 250.