We accept major credit cards and ship worldwide!
Cart 0
LA302  3 wire single phase: 36" leads, 0-300 volts

Delta

LA302 3 wire single phase: 36" leads, 0-300 volts

$71.00

300 Series Specifications

Type of Design Silicon Oxide VaristorTM
Maximum current 100,000 amps
Maximum energy

3,000 joules per pole

Maximum number of surges Unlimited
Response time one milliamp test 5 nanoseconds
Response time to clamp 10,000 amps 10 nanoseconds
Response time to clamp 50,000 amps 25 nanoseconds
Leak current at double the rated voltage none
Leads 36" #12 THHN
Case material PVC
Locknut and Washer 1/2" - 3/4"
Category B & C and Type 1 & 2

Conduction Characteristics

8 x 20 microsecond wave shape
ANSI IEEE NEMA Standard
Discharge Current 5000 A 10000 A 20000 A 40000 A 60000 A 80000 A 100000 A
Clamping Voltage
(Line to Neutral)
240 V 480 V 840 V 1300 V 2000 V 3000 V 4000 V
Unlimited Operations One Operation

Weatherproof N-4
Case Dimensions:
2 1/4" Diameter
4 1/2" High


LA302 - For 120-250 V, Single Phase, 3 Wire Service

Rated voltage 125-250 Volt, three wire service. Used when two hot wires of a single-phase system are to be protected.

INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wires to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal framework of the equipment to be protected or make a ground source per NEC Article 250.


Share this Product